by AMETEK Programmable Power. i / iX / iM Series II AC Power Source User Manual Revision R March 2015 Copyright 2015 by AMETEK Progra
User Manual California Instruments 10 i Series II / iX Series II / iM Series II Figure 4-33: Waveform frequency domain view mode ...
User Manual California Instruments 100 i Series II / iX Series II / iM Series II OPT0, OPT1, OPT2 This field indicates the presence of the foll
User Manual California Instruments i Series II / iX Series II / iM Series II 101 4.2.12 OUTPUT IMPEDANCE Menu [iX Series only] Figure 4-26: O
User Manual California Instruments 102 i Series II / iX Series II / iM Series II 4.2.13 MEASUREMENT CAL FACTORS Menu Figure 4-27: MEASUREMENT
User Manual California Instruments i Series II / iX Series II / iM Series II 103 4.2.14 OUTPUT CAL FACTORS Menu Figure 4-28: OUTPUT CAL FACTOR
User Manual California Instruments 104 i Series II / iX Series II / iM Series II 4.3 Output Programming 4.3.1 Set the Output Output parameters
User Manual California Instruments i Series II / iX Series II / iM Series II 105 To change the output voltage: CounterClockwiseClockwiseINCRDEC
User Manual California Instruments 106 i Series II / iX Series II / iM Series II 4.4 Waveform Management [iX Series only] The iX Series employ
User Manual California Instruments i Series II / iX Series II / iM Series II 107 4.4.3 Creating Custom Waveforms The iX Series provides four gr
User Manual California Instruments 108 i Series II / iX Series II / iM Series II 5. Move the cursor to the MORE field at the end of this menu a
User Manual California Instruments i Series II / iX Series II / iM Series II 109 4.4.6 Frequency Response Restrictions The user may create a wa
User Manual California Instruments i Series II / iX Series II / iM Series II 11 Figure 9-43: OMNI Control Screen ...
User Manual California Instruments 110 i Series II / iX Series II / iM Series II 4.5 Standard Measurements Standard measurements are always ava
User Manual California Instruments i Series II / iX Series II / iM Series II 111 the MEAS key may not always bring up the selected screen immedi
User Manual California Instruments 112 i Series II / iX Series II / iM Series II 4.6 Advanced Measurements [iX Series only] The iX Series offe
User Manual California Instruments i Series II / iX Series II / iM Series II 113 4.6.1.2 Analyzing FFT data The data displays available for FFT
User Manual California Instruments 114 i Series II / iX Series II / iM Series II 4.6.2 Waveform Acquisition The waveform acquisition mode allow
User Manual California Instruments i Series II / iX Series II / iM Series II 115 4.6.2.2 Analyzing waveform data The data displays available fo
User Manual California Instruments 116 i Series II / iX Series II / iM Series II 4.6.3 Triggering Measurements Both FFT results and waveform ac
User Manual California Instruments i Series II / iX Series II / iM Series II 117 This mode is appropriate when capturing analyzing events at a
User Manual California Instruments 118 i Series II / iX Series II / iM Series II This mode is appropriate for capturing the inrush current of
User Manual California Instruments i Series II / iX Series II / iM Series II 119 4.6.3.3 Trigger delay The trigger delay field allows the user
User Manual California Instruments 12 i Series II / iX Series II / iM Series II List of Tables Table 3-1: Wire Sizes ...
User Manual California Instruments 120 i Series II / iX Series II / iM Series II PRE TRIGGER DELAY Alternatively, a negative trigger delay value
User Manual California Instruments i Series II / iX Series II / iM Series II 121 4.7 Transient Programming 4.7.1 Introduction Transient progra
User Manual California Instruments 122 i Series II / iX Series II / iM Series II 4.7.4 Pulse Transients Pulse transients let you program the ou
User Manual California Instruments i Series II / iX Series II / iM Series II 123 4.7.5 List Transients List transients provide the most versati
User Manual California Instruments 124 i Series II / iX Series II / iM Series II 8. The START ø may be left at RANDOM as we are not interested
User Manual California Instruments i Series II / iX Series II / iM Series II 125 Note: The AC source output remains at the last programmed val
User Manual California Instruments 126 i Series II / iX Series II / iM Series II 4.7.7 Switching Waveforms The FUNCTION field available in each
User Manual California Instruments i Series II / iX Series II / iM Series II 127 4.7.8 Transient Execution Figure 4-43: START/VIEW TRANSIENT
User Manual California Instruments 128 i Series II / iX Series II / iM Series II 5. Principle of Operation 5.1 General An explanation of the c
User Manual California Instruments i Series II / iX Series II / iM Series II 129 5.2 Overall Description Three or single phase input power is r
User Manual California Instruments i Series II / iX Series II / iM Series II 13 1. Introduction This instruction manual contains information on
User Manual California Instruments 130 i Series II / iX Series II / iM Series II Figure 5-2: Power Source Module Block Diagram
User Manual California Instruments i Series II / iX Series II / iM Series II 131 5.4 Current Limit Board The current limit board, A6, receives
User Manual California Instruments 132 i Series II / iX Series II / iM Series II 5.6 DC-DC Power Converter The DC-DC power converter, A3, is po
User Manual California Instruments i Series II / iX Series II / iM Series II 133 Figure 5-3: 5001i Internal Layout
User Manual California Instruments 134 i Series II / iX Series II / iM Series II Figure 5-4: Logic Board LED's
User Manual California Instruments i Series II / iX Series II / iM Series II 135 There are six LED indicators on the logic board. Their positio
User Manual California Instruments 136 i Series II / iX Series II / iM Series II Figure 5-5: AC Power Stage Layout Figure 5-6: AC Control Log
User Manual California Instruments i Series II / iX Series II / iM Series II 137 CAUTION VOLTAGES UP TO 480 VAC AND 700 VDC ARE PRESENT IN
User Manual California Instruments 138 i Series II / iX Series II / iM Series II 6. Calibration The Routine Calibration should be performed eve
User Manual California Instruments i Series II / iX Series II / iM Series II 139 6.3 Routine Measurement Calibration Note: The Fluke 8506A Dig
User Manual California Instruments 14 i Series II / iX Series II / iM Series II 1.2 Model Series I and Series II There are several generations
User Manual California Instruments 140 i Series II / iX Series II / iM Series II Figure 6-1: Test Equipment Hook-up for Measurement Calibration
User Manual California Instruments i Series II / iX Series II / iM Series II 141 Note: The Fluke 8506A Digital Multimeter must be used for the f
User Manual California Instruments 142 i Series II / iX Series II / iM Series II 6. When completed, the new cal coefficient will be displayed.
User Manual California Instruments i Series II / iX Series II / iM Series II 143 6.4 Routine Output Calibration Connect the test equipment to t
User Manual California Instruments 144 i Series II / iX Series II / iM Series II Figure 6-2: Test Equipment Hookup for Routine Output Calibrati
User Manual California Instruments i Series II / iX Series II / iM Series II 145 6.5 Output Impedance Calibration Note: Applies to 3001iX, 5001
User Manual California Instruments 146 i Series II / iX Series II / iM Series II These pots were originally adjusted at the factory and normally
User Manual California Instruments i Series II / iX Series II / iM Series II 147 6.6 Non-Routine Calibration All internal adjustments are set a
User Manual California Instruments 148 i Series II / iX Series II / iM Series II 6.6.3 Power Source Gain Adjustment: To make this adjustment th
User Manual California Instruments i Series II / iX Series II / iM Series II 149 7. Service 7.1 Cleaning The exterior of the power source may
User Manual California Instruments i Series II / iX Series II / iM Series II 15 2. Specifications All specifications are for a single i or iX S
User Manual California Instruments 150 i Series II / iX Series II / iM Series II 7.2 General This section describes the suggested maintenance a
User Manual California Instruments i Series II / iX Series II / iM Series II 151 7.3.5 Unit Shuts Down after 1-2 Seconds CAUSE SOLUTION Output
User Manual California Instruments 152 i Series II / iX Series II / iM Series II 7.4 Advanced Troubleshooting. WARNING: Do not connect 400-4
User Manual California Instruments i Series II / iX Series II / iM Series II 153 7.4.4 Fuse Check See Figure 5-3 and Figure 5-5. Check the fus
User Manual California Instruments 154 i Series II / iX Series II / iM Series II FUSE # FUNCTION FUSE VALUE F2 DC-DC Converter logic 1 amp F3
User Manual California Instruments i Series II / iX Series II / iM Series II 155 7.4.6 Disassembly Procedure Disconnect mains power to the sour
User Manual California Instruments 156 i Series II / iX Series II / iM Series II 8. Top Assembly Replaceable Parts Top Assy. No USB Top Assy i
User Manual California Instruments i Series II / iX Series II / iM Series II 157 8.2 Fuses SEQ# CI PART # DESCRIPTION DC - DC POWER ASSY. 7
User Manual California Instruments 158 i Series II / iX Series II / iM Series II 9. Options 9.1 RTCA/DO-160 Option The RTCA/DO-160 Option is m
User Manual California Instruments i Series II / iX Series II / iM Series II 159 9.1.1.3 Tests Performed 9.1.1.3.1 NORMAL STATE AC Source: 1.
User Manual California Instruments 16 i Series II / iX Series II / iM Series II 2.1.2 Output (ALL SPECIFICATIONS ARE FOR AC AND DC UNLESS NOTED
User Manual California Instruments 160 i Series II / iX Series II / iM Series II 9.1.1.4 Front Panel Entry To perform a test from the keyboard
User Manual California Instruments i Series II / iX Series II / iM Series II 161 9.1.1.5 AC TESTS Note: Prior to test selection the standard an
User Manual California Instruments 162 i Series II / iX Series II / iM Series II VOLT FREQ MAX This test will set the voltage and frequency to l
User Manual California Instruments i Series II / iX Series II / iM Series II 163 Figure 9-4: Voltage Modulation
User Manual California Instruments 164 i Series II / iX Series II / iM Series II FREQUENCY MODULATION This test requires a numeric value equal t
User Manual California Instruments i Series II / iX Series II / iM Series II 165 POWER INTERRUPT This test requires a numeric entry value equal
User Manual California Instruments 166 i Series II / iX Series II / iM Series II T1 0 Volt F1 F2
User Manual California Instruments i Series II / iX Series II / iM Series II 167 FREQUENCY TRANSIENTS (Group 1 only) Seq. No Frequency Time 1
User Manual California Instruments 168 i Series II / iX Series II / iM Series II VOLT FREQ MIN Standard/Group RTCA Group1 Group2 Group3 Voltage
User Manual California Instruments i Series II / iX Series II / iM Series II 169 9.1.1.5.3 ABNORMAL TEST From the DO160 MENU Scroll to the ABNO
User Manual California Instruments i Series II / iX Series II / iM Series II 17 Output Parameter i / iM Series iX Series 3001, 9003i/iX 5001
User Manual California Instruments 170 i Series II / iX Series II / iM Series II VOLT MIN This test will set the voltage and frequency to levels
User Manual California Instruments i Series II / iX Series II / iM Series II 171 9.1.1.6 DC TESTS If the output voltage is set for 24V DC or 14
User Manual California Instruments 172 i Series II / iX Series II / iM Series II VOLT MAX Standard Categories A and Z B 28V / 14V RTCA 30.3 3
User Manual California Instruments i Series II / iX Series II / iM Series II 173 9.1.1.6.2 Abnormal Test From the DO-160 MENU scroll to the ABN
User Manual California Instruments 174 i Series II / iX Series II / iM Series II VOLT SURGE This test will produce voltage surge defined by Tabl
User Manual California Instruments i Series II / iX Series II / iM Series II 175 9.2 IEC 61000-4-11 Option 9.2.1 General The IEC1000-4-11 opti
User Manual California Instruments 176 i Series II / iX Series II / iM Series II normally programmed phase angle relationship. For firmware upgr
User Manual California Instruments i Series II / iX Series II / iM Series II 177 Other Dip levels for 2 phase selections. Note that any other di
User Manual California Instruments 178 i Series II / iX Series II / iM Series II 9.2.6.1 DIPS AND INTERRUPTIONS TEST Scroll to the DIPS AND INT
User Manual California Instruments i Series II / iX Series II / iM Series II 179 RUN ALL The RUN ALL selection will cause the following automate
User Manual California Instruments 18 i Series II / iX Series II / iM Series II Figure 2-1: 3001iX / 9003iX - Voltage Current rating, AC mode
User Manual California Instruments 180 i Series II / iX Series II / iM Series II 9.2.6.2 VOLTAGE VARIATION TESTS From the IEC1000-4-11 Main Men
User Manual i Series II / iX Series II / iM Series IIRUN SINGLE RUN SINGLE command will run the test once. The Variation test is defined by the REDUCE
User Manual California Instruments 182 i Series II / iX Series II / iM Series II 9.2.7 Using the GUI Windows Program for IEC 61000-4-11 Testing
User Manual California Instruments i Series II / iX Series II / iM Series II 183 9.3 IEC 61000-4-13 Option 9.3.1 General The IEC413 option is
User Manual California Instruments 184 i Series II / iX Series II / iM Series II Front Panel Entry While it is possible to perform IEC 61000-4-
User Manual California Instruments i Series II / iX Series II / iM Series II 185 EUT CLASS This field selects the desired product or EUT class.
User Manual California Instruments 186 i Series II / iX Series II / iM Series II 9.3.3.2 IEC GROUPS This section will describe the groups and
User Manual California Instruments i Series II / iX Series II / iM Series II 187 SWEEP GROUP If the SWEEP group is selected, the screen will app
User Manual California Instruments 188 i Series II / iX Series II / iM Series II HARMONICS GROUP If the Harmonics group is selected, the screen
User Manual California Instruments i Series II / iX Series II / iM Series II 189 INTERHARMONICS GROUP If the Harmonics group is selected, the sc
User Manual California Instruments i Series II / iX Series II / iM Series II 19 Figure 2-3: 5001iX / 15003iX - Voltage Current rating, AC mode
User Manual California Instruments 190 i Series II / iX Series II / iM Series II MEISTER CURVE GROUP If the Meister curve group is selected, the
User Manual California Instruments i Series II / iX Series II / iM Series II 191 Figure 9-28: IEC 61000-4-13 Test Flowchart Class 1 and 2 S
User Manual California Instruments 192 i Series II / iX Series II / iM Series II Figure 9-29: IEC 61000-4-13 Test Flowchart Class 3 Start - Cla
User Manual California Instruments i Series II / iX Series II / iM Series II 193 To run the test, the IEC 61000-4-13 mode must be selected. Ref
User Manual California Instruments 194 i Series II / iX Series II / iM Series II 9.3.3.4 INTERHARMONICS A single inter harmonic frequency may b
User Manual California Instruments i Series II / iX Series II / iM Series II 195 9.4 EOS Option 9.4.1 Introduction This section contains infor
User Manual California Instruments 196 i Series II / iX Series II / iM Series II 9.4.4 Specifications 9.4.4.1 Input Line Voltage (user configu
User Manual California Instruments i Series II / iX Series II / iM Series II 197 (limited by 5001iX / 15003iX) at 0% UNOM N/A N/A Bypass Mod
User Manual California Instruments 198 i Series II / iX Series II / iM Series II CAUTION Voltages up to 600 VAC are available in certain secti
User Manual California Instruments i Series II / iX Series II / iM Series II 199 9.4.5 Installation and Acceptance 9.4.5.1 Unpacking Inspect t
User Manual California Instruments 2 i Series II / iX Series II / iM Series II User's Manual California Instruments AC Power Source By AMET
User Manual California Instruments 20 i Series II / iX Series II / iM Series II Figure 2-5: 10001iX / 30003iX - Voltage Current rating, AC mode
User Manual California Instruments 200 i Series II / iX Series II / iM Series II 9.4.5.4 Output Wiring The EOS-1 or EOS-3 is wired in series wi
User Manual California Instruments i Series II / iX Series II / iM Series II 201 Figure 9-32: Example Connection With 5001iX and EOS-1
User Manual California Instruments 202 i Series II / iX Series II / iM Series II Figure 9-33: Example Connection With Compliance Test System and
User Manual California Instruments i Series II / iX Series II / iM Series II 203 Figure 9-34: 15003iX-CTS-EOS3-LR3
User Manual California Instruments 204 i Series II / iX Series II / iM Series II Figure 9-35: 15003iX/3-EOS3
User Manual California Instruments i Series II / iX Series II / iM Series II 205 9.4.6 Operation 9.4.6.1 General The EOS-1 is used with a Cali
User Manual California Instruments 206 i Series II / iX Series II / iM Series II 9.4.6.2 Front Panel Controls/Indicators Power Switch and Lamp
User Manual California Instruments i Series II / iX Series II / iM Series II 207 9.4.6.4 EOS3 70/80 Tap setting change Second generation EOS3 u
User Manual California Instruments 208 i Series II / iX Series II / iM Series II Figure 9-36: EOS3 Location of 70/80 Taps for each phase. Lug
User Manual California Instruments i Series II / iX Series II / iM Series II 209 9.4.7 Service and Maintenance 9.4.7.1 Cleaning The exterior o
User Manual California Instruments i Series II / iX Series II / iM Series II 21 Figure 2-7: 15001iX - Voltage Current rating, AC mode Figure
User Manual California Instruments 210 i Series II / iX Series II / iM Series II 9.5 Mode iX Option 9.5.1 Introduction This section contains i
User Manual California Instruments i Series II / iX Series II / iM Series II 211 89 mm H x 480 mm W x 560 mm D Weight 14.1 lbs, 6.39 kg Connect
User Manual California Instruments 212 i Series II / iX Series II / iM Series II CAUTION Voltages up to 600 VAC are available in certain secti
User Manual California Instruments i Series II / iX Series II / iM Series II 213 9.5.3 Installation and Acceptance 9.5.3.1 Unpacking Inspect t
User Manual California Instruments 214 i Series II / iX Series II / iM Series II Note: The SOURCE and LOAD terminals of Mode-iX will be at t
User Manual California Instruments i Series II / iX Series II / iM Series II 215 Figure 9-37: Example Connection With MODE iX
User Manual California Instruments 216 i Series II / iX Series II / iM Series II 9.5.4 Operation 9.5.4.1 General The Mode-iX phase mode contro
User Manual California Instruments i Series II / iX Series II / iM Series II 217 9.5.5 Service and Maintenance 9.5.5.1 Cleaning The exterior o
User Manual California Instruments 218 i Series II / iX Series II / iM Series II 9.6 Omni Options 9.6.1 Introduction This section contains inf
User Manual California Instruments i Series II / iX Series II / iM Series II 219 OMNI Type 1-18i, 3-18i, 1-37i, 3-37i 1-37iJ Impedance ± 5% (
User Manual California Instruments 22 i Series II / iX Series II / iM Series II Figure 2-9: Maximum RMS voltage versus frequency rating in 300V
User Manual California Instruments 220 i Series II / iX Series II / iM Series II For the Omni 1-18i and 3-18i the selector card is marked 100/22
User Manual California Instruments i Series II / iX Series II / iM Series II 221 Refer to the power source manual to determine the appropriate w
User Manual California Instruments 222 i Series II / iX Series II / iM Series II Figure 9-38: Example Connections With OMNI 1-18i
User Manual California Instruments i Series II / iX Series II / iM Series II 223 Figure 9-39: Example Connections With OMNI 3-18i
User Manual California Instruments 224 i Series II / iX Series II / iM Series II Figure 9-40: Schematic Showing OMNI 1-37i and1-37iJ Connected t
User Manual California Instruments i Series II / iX Series II / iM Series II 225 Figure 9-41: Schematic Showing OMNI 3-37i Connected to 30003iX
User Manual California Instruments 226 i Series II / iX Series II / iM Series II 9.6.6 Operation 9.6.6.1 General The OMNI impedance network ad
User Manual California Instruments i Series II / iX Series II / iM Series II 227 Scroll to the OMNI OPTION entry using the up and down courser
User Manual California Instruments 228 i Series II / iX Series II / iM Series II 9.6.6.5 Control Configuration Manual versus programmable cont
User Manual California Instruments i Series II / iX Series II / iM Series II 229 9.7 LNS Option and XLS Option The Line Sync option and the Ext
User Manual California Instruments i Series II / iX Series II / iM Series II 23 Output Parameter i / iM Series iX Series Output Noise: (20 kHz
User Manual California Instruments 230 i Series II / iX Series II / iM Series II 9.7.2 LNS Option (not available with –FC option) The Line Sync
User Manual California Instruments i Series II / iX Series II / iM Series II 231 9.7.4 Mechanical Dimensions Figure 9-45: XLS Module Dimens
User Manual California Instruments 232 i Series II / iX Series II / iM Series II 9.7.5 Connection Diagram The following diagrams illustrate bot
User Manual California Instruments i Series II / iX Series II / iM Series II 233 Figure 9-47:
User Manual California Instruments 234 i Series II / iX Series II / iM Series II 9.7.6 Installation The XLS module can be installed inside a sy
User Manual California Instruments i Series II / iX Series II / iM Series II 235 9.8 Option –704: MilStd704 Tests The MIL704 option is made up
User Manual California Instruments 236 i Series II / iX Series II / iM Series II 9.8.1 Option –704: MIL-STD-704 rev D & E Tests. (Firmware)
User Manual California Instruments i Series II / iX Series II / iM Series II 237 1. Steady State Voltage test 2. Ripple test 9.8.1.4.2 EMERGE
User Manual California Instruments 238 i Series II / iX Series II / iM Series II 9.8.1.6 Revision Selection The default Revision is E. Revision
User Manual California Instruments i Series II / iX Series II / iM Series II 239 • 112V for 1 minute. • 118V for 1 minute. • 115V for 1 minut
User Manual California Instruments 24 i Series II / iX Series II / iM Series II Parameter Range Accuracy (±) Resolution Accuracy specifications
User Manual California Instruments 240 i Series II / iX Series II / iM Series II 9.8.1.7.2 TRANSIENT TEST From the MIL704 main menu (Figure 9-4
User Manual California Instruments i Series II / iX Series II / iM Series II 241 This test will change the output frequency in the following seq
User Manual California Instruments 242 i Series II / iX Series II / iM Series II 9.8.1.7.4 ABNORMAL TEST From the MIL704 main menu (Figure 9-49
User Manual California Instruments i Series II / iX Series II / iM Series II 243 • 0Hz for 7 seconds. • 380Hz for 7 seconds. The ← key (backsp
User Manual California Instruments 244 i Series II / iX Series II / iM Series II ±1.5V. 2. 270V system: ±6.0V. The ← key (backspace) will termi
User Manual California Instruments i Series II / iX Series II / iM Series II 245 2. 270V System • 200V for 10 msec. • Linearly increase to 25
User Manual California Instruments 246 i Series II / iX Series II / iM Series II • 0V for 7sec. • 20V for 93sec. 2. 270V system: • 0V for 7s
User Manual California Instruments i Series II / iX Series II / iM Series II 247 9.9 ABD Option: Airbus ABD0100.1.8 Test For information regard
User Manual California Instruments 248 i Series II / iX Series II / iM Series II 9.13 WHM Option 9.13.1 General This section describes the WHM
User Manual California Instruments i Series II / iX Series II / iM Series II 249 Note: Changing from stop to start will stop the measurement a
User Manual California Instruments i Series II / iX Series II / iM Series II 25 Parameter Specification Note: Disconnect any USB connection when
User Manual California Instruments 250 i Series II / iX Series II / iM Series II 9.13.4 Remote PROGRAMMING The following SCPI command will be u
User Manual California Instruments i Series II / iX Series II / iM Series II 251 Error Messages Any errors that occur during operation from eith
User Manual California Instruments 252 i Series II / iX Series II / iM Series II Number Message String Cause Remedy allowed" correct c
User Manual California Instruments i Series II / iX Series II / iM Series II 253 Number Message String Cause Remedy -300 "Device specif
User Manual California Instruments 254 i Series II / iX Series II / iM Series II Number Message String Cause Remedy 6 "Limit memory los
User Manual California Instruments i Series II / iX Series II / iM Series II 255 Number Message String Cause Remedy 23 "ALC or Impedanc
User Manual California Instruments 256 i Series II / iX Series II / iM Series II 10. Index+ +/- key ...
User Manual California Instruments i Series II / iX Series II / iM Series II 257 Hold-Up Time ... 1
User Manual California Instruments i Series II / iX Series II / iM Series II 258sense ...
User Manual California Instruments 26 i Series II / iX Series II / iM Series II 2.2 Mechanical Parameter Specification Dimensions: 19” (483 mm
User Manual California Instruments i Series II / iX Series II / iM Series II 27 2.4 Regulatory Electromagnetic Emissions and Immunity: Designed
User Manual California Instruments 28 i Series II / iX Series II / iM Series II 2.6 Special Features, Options and Accessories Feature Descripti
User Manual California Instruments i Series II / iX Series II / iM Series II 29 provided on CD ROM CIC496. -AMD Airbus AMD24C Test software (re
User Manual California Instruments i Series II / iX Series II / iM Series II 3 About AMETEK AMETEK Programmable Power, Inc., a Division of AMETE
User Manual California Instruments 30 i Series II / iX Series II / iM Series II 2.7.1 Output Output Parameter Voltage: Slew rate: > 0.5 V/m
User Manual California Instruments i Series II / iX Series II / iM Series II 31 3. Unpacking and Installation 3.1 Unpacking Inspect the unit
User Manual California Instruments 32 i Series II / iX Series II / iM Series II 3.3 Mechanical Installation The 3001i/iX and 5001i/iX are compl
User Manual California Instruments i Series II / iX Series II / iM Series II 33 The output power cables must be large enough to prevent a total
User Manual California Instruments 34 i Series II / iX Series II / iM Series II 3.6 Connectors - Rear Panel A number of connectors are located
User Manual California Instruments i Series II / iX Series II / iM Series II 35 J22 Description J22-32. 16 AMP SHARE B 17 PARALLEL 18 CL EN
User Manual California Instruments 36 i Series II / iX Series II / iM Series II 3.6.2 Remote Sense Connector TB3 When selecting external sense
User Manual California Instruments i Series II / iX Series II / iM Series II 37 3.6.3 RS232C Serial Interface Connector – J18 Note that two ver
User Manual California Instruments 38 i Series II / iX Series II / iM Series II Figure 3-2: RS232C Cable for PC Connection wiring diagram – Uni
User Manual California Instruments i Series II / iX Series II / iM Series II 39 3.6.5 LAN Interface – RJ45 An optional RJ45 Ethernet 10BaseT co
User Manual California Instruments 4 i Series II / iX Series II / iM Series II Important Safety Instructions Before applying power to the system
User Manual California Instruments 40 i Series II / iX Series II / iM Series II 3.6.6 I/O Option – J58 This connector is reserved for control o
User Manual California Instruments i Series II / iX Series II / iM Series II 41 Figure 3-5: Function Strobe / Trigger Output Accessory.
User Manual California Instruments 42 i Series II / iX Series II / iM Series II 3.6.8 Remote Inhibit – J22-36 / J22-27 The Remote Inhibit input
User Manual California Instruments i Series II / iX Series II / iM Series II 43 Figure 3-6: Rear Panel View for the 3001i/3001iX (Series II)
User Manual California Instruments 44 i Series II / iX Series II / iM Series II Figure 3-7: Rear Panel View for the 3001i/3001iX (Series I, no U
User Manual California Instruments i Series II / iX Series II / iM Series II 45 Figure 3-8: Rear Panel View for the 5001i/5001iX (Series II)
User Manual California Instruments 46 i Series II / iX Series II / iM Series II Figure 3-9: Rear Panel View for the 5001i/5001iX (Series I, no U
User Manual California Instruments i Series II / iX Series II / iM Series II 47 3.7 Single-Phase and Three Phase Multiple Box System Configurat
User Manual California Instruments 48 i Series II / iX Series II / iM Series II 4. Press “ENTER” and the unit will display the Program selectio
User Manual California Instruments i Series II / iX Series II / iM Series II 49 Figure 3-10: Connection For Single Power Source (5001iX/i, 3001i
User Manual California Instruments i Series II / iX Series II / iM Series II 5
User Manual 50 i Series II / iX Series II / iM Series IIFigure 3-11: Functional Test Setup California Instruments i Series II / iX Series II / iM S
User Manual California Instruments i Series II / iX Series II / iM Series II 51 Figure 3-12: Single Phase 10000 VA System (10001iX/i)
User Manual California Instruments 52 i Series II / iX Series II / iM Series II Figure 3-13: Two Phase 10000 VA System (10002i/iX – One Controll
User Manual California Instruments i Series II / iX Series II / iM Series II 53 Figure 3-14: Three Phase 15000 VA System (15003iX/i-LK Three Co
User Manual California Instruments 54 i Series II / iX Series II / iM Series II Figure 3-15: Single Phase 15000 VA System (15001iX/i)
User Manual California Instruments i Series II / iX Series II / iM Series II 55 Figure 3-16: Three-Phase 15000 VA system (15003iX/i - One Contr
User Manual California Instruments 56 i Series II / iX Series II / iM Series II Figure 3-17: Connection With MODE Option
User Manual California Instruments i Series II / iX Series II / iM Series II 57 Figure 3-18: Two Phase 10000 VA System (10002i-LK Two Controlle
User Manual California Instruments 58 i Series II / iX Series II / iM Series II Figure 3-19: Three-Phase 9000 VA System (9003iX/i – One Control
User Manual California Instruments i Series II / iX Series II / iM Series II 59 4. Front Panel Operation 4.1 Tour of the Front Panel The i, iM
User Manual California Instruments 6 i Series II / iX Series II / iM Series II Product Family: iM /i / iX Series AC Power Source Warranty Period
User Manual California Instruments 60 i Series II / iX Series II / iM Series II OVER TEMPERATURE The OVER TEMPERATURE LED indicates an overheat
User Manual California Instruments i Series II / iX Series II / iM Series II 61 4.1.5 FUNCTION Keypad The function keypad provides access to al
User Manual California Instruments 62 i Series II / iX Series II / iM Series II OUTPUT ON/OFF The OUTPUT ON/OFF key toggles the output relay on
User Manual California Instruments i Series II / iX Series II / iM Series II 63 CURSOR UP The UP key moves the cursor position upwards one posi
User Manual California Instruments 64 i Series II / iX Series II / iM Series II 4.1.7 LCD Display The LCD display of the i and iX Series AC pow
User Manual California Instruments i Series II / iX Series II / iM Series II 65 4.2 Menu Structure The next few pages show a map of the availab
User Manual California Instruments 66 i Series II / iX Series II / iM Series II The following top-level menu choices can be accessed from the ME
User Manual California Instruments i Series II / iX Series II / iM Series II 67 4.2.2 Overview of Menu 1 level 1 level 2 level 3
User Manual California Instruments 68 i Series II / iX Series II / iM Series II 4.2.3 Overview of Menu 2 and 3 level 1 level 2 level 3
User Manual California Instruments i Series II / iX Series II / iM Series II 69 4.2.4 PROGRAM Menu Figure 4-8: PROGRAM Menu The PROGRAM men
User Manual California Instruments i Series II / iX Series II / iM Series II 7 Table of Contents 1. Introduction ...
User Manual California Instruments 70 i Series II / iX Series II / iM Series II PROGRAM 2 PHASE Selects the phase angle between the external cl
User Manual California Instruments i Series II / iX Series II / iM Series II 71 4.2.5 MEASUREMENTS Screens The i/iX Series uses a DSP based dat
User Manual California Instruments 72 i Series II / iX Series II / iM Series II POWER FACTOR This readout shows the power factor of the load. C
User Manual California Instruments i Series II / iX Series II / iM Series II 73 HARMONICS/TRACE ANALYSIS Screen [iX Series only] The fourth mea
User Manual California Instruments 74 i Series II / iX Series II / iM Series II This mode does not apply to the TRACE view display mode and is
User Manual California Instruments i Series II / iX Series II / iM Series II 75 capability for the waveshape selected on the phase or phases pro
User Manual California Instruments 76 i Series II / iX Series II / iM Series II 4.2.6 TRANSIENTS Menu Figure 4-11: TRANSIENTS menu The transi
User Manual California Instruments i Series II / iX Series II / iM Series II 77 4.2.6.1 VOLT SURGE/SAG sub menu Figure 4-12: VOLTAGE SURGE/SA
User Manual California Instruments 78 i Series II / iX Series II / iM Series II REPEAT This is the number of times the SURGE/SAG transient even
User Manual California Instruments i Series II / iX Series II / iM Series II 79 4.2.6.2 VOLTAGE SWEEP/STEP sub menu Figure 4-13: VOLTAGE SWEE
User Manual California Instruments 8 i Series II / iX Series II / iM Series II 7. Service ...
User Manual California Instruments 80 i Series II / iX Series II / iM Series II REPEAT This is the number of times the VOLTAGE SWEEP/STEP trans
User Manual California Instruments i Series II / iX Series II / iM Series II 81 4.2.6.3 FREQUENCY SWEEP/STEP sub menu Figure 4-14: FREQUENCY
User Manual California Instruments 82 i Series II / iX Series II / iM Series II 4.2.6.4 VOLTAGE/FREQUENCY SWEEP/STEP sub menu Figure 4-15: VO
User Manual California Instruments i Series II / iX Series II / iM Series II 83 EVENT # This must be the last item in the transient edit screen
User Manual California Instruments 84 i Series II / iX Series II / iM Series II 4.2.7 WAVEFORMS Menu [iX Series only] Figure 4-17: WAVEFORMS
User Manual California Instruments i Series II / iX Series II / iM Series II 85 VIEW(F): This mode can be used to display any of the availab
User Manual California Instruments 86 i Series II / iX Series II / iM Series II A right arrow indicates the waveform is presently selected for
User Manual California Instruments i Series II / iX Series II / iM Series II 87 4.2.8 ADVANCE MEAS. Menu [iX Series only] This entry in the ME
User Manual California Instruments 88 i Series II / iX Series II / iM Series II 4.2.10 SETUP REGISTERS Menu Figure 4-19: SETUP REGISTERS menu
User Manual California Instruments i Series II / iX Series II / iM Series II 89 4.2.11 UTILITY Menus Figure 4-20: UTILITY menus The UTILITY
User Manual California Instruments i Series II / iX Series II / iM Series II 9 List of Figures Figure 2-1: 3001iX / 9003iX - Voltage Current rat
User Manual California Instruments 90 i Series II / iX Series II / iM Series II INITIAL SETUP The initial setup menu can be used to determine t
User Manual California Instruments i Series II / iX Series II / iM Series II 91 ELAPSED TIME The elapsed time screen, when selected from the UT
User Manual California Instruments 92 i Series II / iX Series II / iM Series II 4.2.11.1 GPIB/RS232 (incl. USB/LAN) SETUP menu Figure 4-21: G
User Manual California Instruments i Series II / iX Series II / iM Series II 93 4.2.11.2 VOLTAGE/CURRENT CONTROL SETUP menu Figure 4-22: VOLT
User Manual California Instruments 94 i Series II / iX Series II / iM Series II VOLT SENSE This field selects the internal or external sense li
User Manual California Instruments i Series II / iX Series II / iM Series II 95 4.2.11.3 INITIAL SETUP menu Figure 4-23: INITIAL SETUP menu
User Manual California Instruments 96 i Series II / iX Series II / iM Series II WAVE GROUP [iX Series only] Sets the user defined waveform grou
User Manual California Instruments i Series II / iX Series II / iM Series II 97 4.2.11.4 LIMIT SETUP screen Figure 4-24:LIMIT SETUP menu The l
User Manual California Instruments 98 i Series II / iX Series II / iM Series II 4.2.11.5 CONFIGURATION SETUP screens Fig
User Manual California Instruments i Series II / iX Series II / iM Series II 99 CLOCK/LOCK Indicates the presence of the -LKS clock and lock au